Voltage drop
Single-phase and three-phase, solving for volts, percent, size or length.
Read the worked examplesJourneyman electrician exam / calculations
Voltage drop, conduit fill, box fill, load calcs, Ohm's law, ampacity and derating. Every line of the math written out, with the NEC table you would open for each number.
12 AWG copper, 20 A, 100 ft one way, 120 V single-phase.
What it covers
Each topic is broken into the same pattern: the formula, where every number comes from, then worked problems with the traps marked.
Single-phase and three-phase, solving for volts, percent, size or length.
Read the worked examplesChapter 9 Tables 1, 4 and 5, the ground you must count, and the 0.8 rule.
Read the worked examplesWhat counts as 1, what counts as 2, and what does not count at all.
Read the worked examplesThe dwelling standard method in order, ending at the service conductors.
Read the worked examplesHeaters, parallel loads, power factor and three-phase power.
Read the worked examplesTemperature correction, bundling, and the terminal check.
Read the worked examplesThe format
This is how each exercise is laid out: the givens, one step per line, and the answer with the code reference. In the course app you answer first, then the steps animate in one at a time, and points, streaks and levels track your progress.
Check it in the calculatorA 240 V single-phase load draws 30 A. It is 150 ft from the panel on 10 AWG copper. What is the voltage drop in percent, and does it meet the 3% recommendation?
Pick the single-phase formula
VD = 2 × K × I × L / CMPlug in the numbers
VD = 2 × 12.9 × 30 × 150 / 10,380Multiply the top, then divide
VD = 116,100 / 10,380 = 11.18 VConvert to percent and compare
11.18 / 240 × 100 = 4.66% > 3%4.66%, over the 3% recommendation. 8 AWG copper (16,510 cmil) brings it to 7.03 V, or 2.93%. CM values: NEC Chapter 9, Table 8.
Free tool
Single-phase or three-phase, copper or aluminum, 14 AWG to 500 kcmil. It shows the drop in volts and percent, compares it to the 3% recommendation, and writes out every step so you can check your own work line by line.
Open the calculatorRecent articles
Nine current-carrying 10 AWG THHN conductors at 40°C: start at 90°C, apply 0.91 and 0.70, then check the terminal. The answer is 25.48 A.
Main, system and equipment bonding jumpers compared side by side: what each one joins, where it is used, and how to tell them apart on the exam.
Size motor overload protection from the nameplate under NEC 430.32: when 125% applies, when 115% applies, and a full worked example.
Width, height, depth, doors and storage around electrical equipment under NEC 110.26, with a seven-question quiz and a one-page checklist.
Free
Voltage drop, conduit fill, box fill, Ohm's law and derating. One problem each, solved line by line. They open right after you sign up.

308 worked exercises in the seven calculation types, four timed practice exams, and a practice app that shows every step after you answer.
$59 one-time, lifetime access
One-time payment, instant access in the practice app. 30-day refund, see the terms.