Ampacity
Ampacity With 9 Conductors in One Conduit: Derating Worked Example
Nine current-carrying 10 AWG copper THHN conductors in one conduit, in a 40°C ambient, on 75°C terminals, have a usable ampacity of 25.48 A. You get there by starting at the 90°C column (40 A), multiplying by the ambient correction (0.91) and by the adjustment for nine conductors (0.70), then checking that the result is below the terminal limit.
This article works through that example one step at a time. Section and table references follow the 2020 and 2023 editions of NFPA 70, where the ambient correction table and the bundling adjustment table sit in 310.15. Confirm the edition your state has adopted and read the actual text in your code book.
The four steps in order
- Base ampacity. Read the conductor in the 90°C column of Table 310.16, because THHN is rated 90°C. The 90°C value is the starting point for correction and adjustment.
- Ambient temperature correction. Multiply by the factor for the ambient temperature, taken from the same 90°C column.
- Adjustment for bundling. Multiply by the factor for the number of current-carrying conductors in the raceway or cable.
- Terminal limit. Compare the result with the ampacity in the 60°C or 75°C column that applies at the terminals. The lower value wins.
The numbers used here
For copper, Table 310.16 lists 10 AWG at 30 A in the 60°C column, 35 A in the 75°C column and 40 A in the 90°C column. The ambient correction factors for the 90°C column are 0.96 for 31 through 35°C, 0.91 for 36 through 40°C and 0.87 for 41 through 45°C. The adjustment factors for the number of current-carrying conductors are listed below.
| Current-carrying conductors | Adjustment factor |
|---|---|
| 4 through 6 | 80% |
| 7 through 9 | 70% |
| 10 through 20 | 50% |
| 21 through 30 | 45% |
Worked example
Nine current-carrying 10 AWG copper THHN conductors share a conduit. The ambient temperature is 40°C. The terminals are rated 75°C.
- Base value from the 90°C column: 40 A.
- Ambient correction at 40°C: 40 × 0.91 = 36.4 A.
- Adjustment for nine conductors: 36.4 × 0.70 = 25.48 A.
- Terminal limit: the 75°C column for 10 AWG is 35 A.
- 25.48 A is lower than 35 A, so 25.48 A is the usable ampacity.
Answer: 25.48 A. The two corrections are both needed. If you stop after the ambient step you get 36.4 A, which is too high. If you start from the 75°C column and then correct, you get a lower number than you are entitled to, because the 90°C value is the proper starting point.
Why the terminal check is last
Section 110.14(C) says the temperature rating of a conductor cannot be used above the lowest rating of any connected termination or device. Starting from 90°C and correcting downward usually leaves you far below the terminal limit when many conductors are bundled, so the terminal check does not change the answer here. With only a few conductors in a cool ambient, the check is what stops you from using too high a number. See our guide to terminal temperature ratings for examples where the terminal wins.
Common mistakes
- Applying only the bundling factor and forgetting the ambient correction, or the other way around.
- Starting from the 60°C or 75°C column and then applying both factors, which undercounts the ampacity.
- Using the 80 percent factor for nine conductors. Four through six take 80 percent, seven through nine take 70 percent.
- Counting an equipment grounding conductor as current-carrying. It is not counted.
- Reading the ambient factor from the wrong column. Match the factor column to the insulation rating you started from.
A quick check on the arithmetic
Because the factors multiply, you can combine them first: 0.91 × 0.70 = 0.637. Then 40 × 0.637 = 25.48 A. If your exam question gives a calculator-friendly answer such as 25.48 A, you can confirm the order does not matter, but you must still use both factors. For a step-by-step comparison with fewer conductors, read our guide to ampacity derating for temperature and bundling.
Practice problem
Six current-carrying 12 AWG copper THHN conductors share a conduit in a 35°C ambient. The terminals are rated 75°C. What is the usable ampacity?
- Base value, 90°C column: 30 A.
- Ambient correction at 35°C: 30 × 0.96 = 28.8 A.
- Adjustment for six conductors: 28.8 × 0.80 = 23.04 A.
- Terminal limit, 75°C column for 12 AWG: 25 A.
- 23.04 A is lower than 25 A, so the usable ampacity is 23.04 A.
Notice that the terminal limit was close this time. If the bundle had been three conductors in a cool room, the corrected number could have been above 25 A, and the terminal would have set the answer. Always run the last step, even when you expect the corrections to be enough on their own. It takes a few seconds and it is the step graders look for.
Where to read more
The NEC is published by NFPA and can be read free online with an account at NFPA 70 on nfpa.org. Ambient correction values are tabulated in the Elliott Electric correction factor reference, and the bundling adjustment is tabulated in their conductor derating reference. The base ampacities are published in the Table 310.16 summary from LugsDirect. These are secondary references, so use them to check your work and your own code book for the current text.
CircuitDrill is an independent study tool and is not affiliated with NFPA, the NEC or any exam provider. Confirm requirements with the authority having jurisdiction (AHJ). To practice more calculations like this one, see the calculations course.
Frequently asked questions
What is the adjustment factor for 9 current-carrying conductors?
70 percent for 7 through 9 current-carrying conductors in a raceway or cable, from the adjustment table in 310.15. Four to six conductors take 80 percent, and 10 through 20 take 50 percent.
Do I apply the ambient correction and the bundling adjustment together?
Yes. Start from the 90°C column for THHN, multiply by the ambient correction factor, then by the adjustment factor, and finally compare the result with the terminal limit. The lower value is the usable ampacity.
Which ambient correction factor applies at 40°C?
For the 90°C column, 36 through 40°C ambient uses 0.91, and 31 through 35°C uses 0.96. Always read the factor from the column that matches the insulation you started from.
Does the equipment grounding conductor count as current-carrying?
No. A grounding or bonding conductor is not counted. A neutral is counted only in specific cases, such as a major part of the load being nonlinear. Check the counting rules in your adopted edition of 310.15.
Free
Get 5 worked problems right away
Voltage drop, conduit fill, box fill, Ohm's law and derating. One problem each, solved line by line. They open right after you sign up.