Terminal Temperature Ratings: 60°C vs 75°C Ampacity, Worked Examples

/ 7 min read / By CircuitDrill

You can find a conductor's ampacity in Table 310.16 in about ten seconds. The harder question is which column to read. A THHN conductor has a 90°C insulation rating, yet in most field installs you cannot use the 90°C number as the final answer. The reason is NEC 110.14(C), the rule about temperature limitations at terminals. This article works through it with numbers.

Section references and table values follow the 2020 and 2023 editions of NFPA 70. Confirm the edition your state has adopted, read the actual text in your code book, and check with the authority having jurisdiction (AHJ) when you are not sure.

The idea in one sentence

Section 110.14(C) says the temperature rating of a conductor must not exceed the lowest temperature rating of any connected termination, conductor or device. In plain words: the weakest link in the connection sets the limit. A wire can survive 90°C, but a breaker lug or a device terminal that is only tested at 60°C or 75°C is part of the connection too.

Which column applies

For the common cases, the code sorts terminals by the size of the circuit:

  • 100 A or less, or equipment marked for 14 AWG through 1 AWG: use the 60°C column of Table 310.16 unless the equipment listing or marking says otherwise. Conductors rated 75°C or higher may be used, but the ampacity is taken from the 60°C column.
  • Over 100 A, or equipment marked for conductors larger than 1 AWG: use the 75°C column, again subject to the listing and marking.
  • Adjustment and correction: a conductor with a higher temperature rating than the terminals may be used to start the derating calculation, but the final ampacity must still comply with 110.14(C).

Other provisions in 110.14(C) cover special cases, such as certain motor circuits. For the exam, always read the question for a listing, marking or special equipment before you pick a column.

Copper ampacity values for practice

These are the copper values commonly published from Table 310.16. Check them against your own code book before you rely on them.

AWG60°C75°C90°C
840 A50 A55 A
655 A65 A75 A
470 A85 A95 A
385 A100 A115 A
295 A115 A130 A
1110 A130 A145 A
1/0125 A150 A170 A

Example 1: the 60°C column sets the size

A circuit needs 90 A of ampacity. It is protected by a 100 A breaker, and neither the breaker nor the device it feeds has any special marking.

  1. The circuit is 100 A or less, so use the 60°C column.
  2. 3 AWG copper is 85 A in that column. That is too low.
  3. 2 AWG copper is 95 A in that column. That is enough.

Answer: 2 AWG. If you read the 75°C column by mistake, 3 AWG shows 100 A and looks fine, which is the classic wrong answer. The 3 AWG conductor would work only if the equipment is listed and marked for use at 75°C.

Example 2: starting from 90°C for derating

Four current-carrying 1 AWG copper THHN conductors share a raceway. They terminate on equipment rated over 100 A with 75°C terminals.

  1. Start with the 90°C column: 145 A.
  2. Four to six current-carrying conductors take an 80 percent adjustment factor from Table 310.15(C)(1): 145 × 0.80 = 116 A.
  3. Check the terminal limit. The 75°C column for 1 AWG is 130 A.
  4. 116 A is lower than 130 A, so 116 A is the usable ampacity.

Compare that with starting from the 75°C column: 130 × 0.80 = 104 A. This is why the 90°C rating of THHN is valuable. It does not raise the final ampacity above the terminal limit, but it gives a better starting point when the wire is derated.

Example 3: when the terminal wins

Now take four current-carrying 4 AWG copper THHN conductors on a device rated 100 A or less with 60°C terminals.

  1. 90°C column: 95 A.
  2. Adjustment: 95 × 0.80 = 76 A.
  3. Terminal limit: the 60°C column for 4 AWG is 70 A.
  4. 70 A is lower than 76 A, so 70 A is the limit.

Here the adjusted number looks fine, but the terminal cap is lower. The rule is simple: do the adjustment, then compare with the terminal column, then take the lower value.

Common mistakes

  • Using the 90°C column as the final answer because the insulation says THHN.
  • Using the 75°C column for a 100 A or smaller circuit without a listing or marking that allows it.
  • Forgetting that the 90°C value is a starting point for adjustment and correction only.
  • Reading only the breaker and ignoring the device or lug at the other end of the conductor.
  • Ignoring other limits that apply, such as the overcurrent protection rules in 240.4.

For more on bundling and ambient temperature, read our guide to ampacity and derating.

Where to read more

The NEC is published by NFPA and can be read free online with an account at NFPA 70 on nfpa.org. For a table of ampacity values, see WireRef's Table 310.16 summary. A step-by-step explanation of applying correction and adjustment before the terminal check is in the NEC Mastery guide to ampacity adjustments, and an Electrical Contractor magazine column discusses 110.14(C) in the general installation requirements series. That column is older, so use it for the idea and your own code book for the current text.

Practice

If you want more worked calculations like these, the CircuitDrill calculations course covers the math side of the journeyman exam, and the blog index lists the rest of the guides. CircuitDrill is an independent study tool and is not affiliated with NFPA, the NEC or any exam provider.

Frequently asked questions

Why can't I use the 90°C column for THHN wire as the final ampacity?

Under 110.14(C) the conductor temperature rating must not exceed the lowest rating of any connected termination, conductor or device. The 90°C value can be the starting point for adjustment and correction, but the final ampacity must still comply with the terminal limit.

Which column applies to a 100 A or smaller circuit?

Generally the 60°C column of Table 310.16, unless the equipment listing or marking says otherwise. Equipment marked for conductors from 14 AWG through 1 AWG is treated the same way.

Which column applies above 100 A?

Generally the 75°C column, for circuits over 100 A or equipment marked for conductors larger than 1 AWG, again subject to listing and marking.

Does the 90°C rating of THHN ever help?

Yes. It lets you start a derating calculation from the 90°C column. For example, 1 AWG at 145 A with an 80 percent factor gives 116 A, which is higher than starting from 130 A at 75°C.