Pull Box Sizing: Straight Pull and Angle Pull Worked Example

/ 7 min read / By CircuitDrill

Pull box sizing questions look intimidating, but the whole topic comes down to two multipliers and one habit: calculate each wall on its own. Section 314.28 tells you the minimum size of a pull or junction box that has large conductors running through it. This guide works one box from start to finish, a straight pull first and then an angle pull.

Edition check: subsection numbers here, 314.28(A)(1) and (A)(2), follow the way the NEC 2020 and 2023 editions are commonly cited. Study sources note that wording in this section has been revised in recent code cycles, so read the exact text in the edition your state has adopted, and ask the authority having jurisdiction (AHJ) about any local rule. This is a study aid, not an installation instruction.

When 314.28 applies

Section 314.28 covers pull and junction boxes that enclose conductors 4 AWG or larger. For boxes with only smaller conductors, you are in the box fill rules of 314.16 instead. If you want that side of the topic, the box fill calculation guide covers it.

Two vocabulary points before the math. "Trade size" means the nominal size of the raceway, such as 2, 2-1/2 or 3 inches. A "row" means the raceways entering the same wall of the box, lined up together. And in an angle pull, the conductors leave through a different wall than the one they entered.

The straight pull: 8 times

In a straight pull, conductors enter one wall and leave through the opposite wall. Under 314.28(A)(1), the length of the box must not be less than eight times the trade size of the largest raceway.

Example. A 3-inch raceway enters the left wall and a 3-inch raceway leaves the right wall.

  • Largest raceway: 3 in
  • Minimum length: 8 × 3 = 24 inches

With a 2-1/2 inch raceway the same rule gives 8 × 2.5 = 20 inches.

The angle pull: 6 times, plus the others

When conductors enter through one wall and leave through another, 314.28(A)(2) applies. For each row of raceways, take six times the trade size of the largest raceway in that row, then add the trade sizes of the other raceways in that row. That result is the minimum distance from the raceway entry to the wall opposite it. A U pull, where conductors leave through the same wall they entered, is handled with the same row method.

Calculate every row separately. If one wall has two rows, do not add the rows together. The row that gives the largest distance sets that dimension of the box.

Worked example

The left wall of a pull box has one row of three raceways: a 3-inch and two 2-inch. The conductors turn and leave through the top wall in a single 3-inch raceway.

  1. Left wall row. Largest raceway is 3 in. Six times 3 is 18. Add the other raceways: 2 + 2 = 4. Total: 18 + 4 = 22 inches. This is the minimum distance from the left wall to the opposite wall, so the box must be at least 22 inches wide.
  2. Top wall. One 3-inch raceway. Six times 3 = 18 inches. This is the minimum distance from the top wall to the bottom wall, so the box must be at least 18 inches tall.
  3. Distance between entries. The 3-inch raceway on the left wall and the 3-inch raceway on the top wall enclose the same conductors. The distance between them must be at least 6 × 3 = 18 inches, measured from the nearest edge of one entry to the nearest edge of the other. A box that is 22 by 18 does not prove this by itself, so check where the raceways actually land.

The minimum box is therefore 22 inches by 18 inches, plus enough depth for the fittings, bending space and anything else the installation needs.

Two rows on one wall

Now suppose one wall carries two rows.

  • Row 1: a 3-inch and a 2-inch raceway. 6 × 3 + 2 = 20 inches.
  • Row 2: a 4-inch and a 1-1/2 inch raceway. 6 × 4 + 1.5 = 25.5 inches.

The larger result governs. This wall needs 25.5 inches, not 45.5. The rows are not added together.

Both kinds of pull in the same box

If a box has a straight pull and an angle pull in the same direction, it must meet both. Work out each dimension both ways and keep the larger number. Study references also note that, for conductors in cables, you use the smallest raceway trade size that would be permitted for the conductors in the cable.

A summary you can scan

Pull typeFormulaExample
Straight8 × largest trade size8 × 3 = 24 in
Angle or U, one row6 × largest + sum of the others6 × 4 + 3 + 2 = 29 in
Two rows, one wallCompute each row, keep the larger20 and 25.5, so 25.5 in
Same conductors, two entriesAt least 6 × the larger raceway apart6 × 3 = 18 in

Common mistakes

  • Adding every raceway on the wall, instead of 6 times the largest plus the others. For a row of 4, 3 and 2 inch raceways that gives 54 inches by mistake, when the correct answer is 29.
  • Using 8 times for an angle pull, or 6 times for a straight pull.
  • Adding two rows together instead of keeping the larger.
  • Forgetting the separate distance between entries for the same conductors.
  • Applying 314.28 to conductors smaller than 4 AWG.

Check yourself

Try these, then compare. A 2-1/2 inch straight pull: 8 × 2.5 = 20 inches. An angle pull row of 4, 3 and 2 inch raceways: 6 × 4 + 3 + 2 = 29 inches. Rows that calculate to 23 and 25.5 inches: 25.5 inches governs.

Where to read more

NFPA publishes the code on its NFPA 70 (NEC) page. A 314.28 section reference quotes the straight pull rule, and this pull box sizing study guide works similar examples. The study guide follows a newer edition than the 2020 and 2023 numbering used above, so confirm each point in your own code book.

Practice it

For each box, ask three questions in order: are the conductors 4 AWG or larger, which walls do the conductors use, and what does each row give? The CircuitDrill course has more worked problems in this style. CircuitDrill is an independent study resource, not affiliated with NFPA or any licensing board. Follow the adopted code and your AHJ for real work.

Frequently asked questions

When does 314.28 apply instead of box fill in 314.16?

Section 314.28 covers pull and junction boxes that enclose conductors 4 AWG or larger. Boxes with only smaller conductors fall under the box fill rules of 314.16. Confirm the wording in your adopted edition.

How long must a box be for a straight pull?

At least eight times the trade size of the largest raceway. For a 3-inch raceway that is 8 x 3 = 24 inches.

How do I size a box for an angle pull?

For each row, take six times the trade size of the largest raceway in that row, then add the trade sizes of the other raceways in the same row. Calculate each row separately and keep the larger result for that dimension.

Do I add two rows on the same wall together?

No. Each row is calculated on its own and the larger result governs. Rows of 20 and 25.5 inches give 25.5 inches, not 45.5.