EGC vs GEC Sizing: Table 250.122 vs Table 250.66

/ 7 min read / By CircuitDrill

Two grounding tables show up on almost every journeyman exam, and they look alike enough that candidates swap them under time pressure. Table 250.122 sizes the equipment grounding conductor. Table 250.66 sizes the grounding electrode conductor. They answer different questions, and each one starts from a different input. This guide puts them side by side, then works one panel through both.

Edition check: section and table numbers here follow the NEC 2020 and 2023 editions. The lettering of paragraphs inside 250.122 can differ in other editions, so read the text in the edition your state has adopted, and ask the authority having jurisdiction (AHJ) if anything is unclear. This is a study aid, not an installation instruction.

Two conductors, two jobs

The equipment grounding conductor (EGC) is the ground-fault current path. It ties together the normally non-current-carrying metal parts of a circuit, such as boxes, enclosures and frames, and connects them back to the system grounded conductor or the grounding electrode conductor. NFPA's grounding and bonding fact sheet describes it that way, and notes that Table 250.122 sizes it from the overcurrent device protecting the circuit.

The grounding electrode conductor (GEC) connects the system grounded conductor, or equipment, to a grounding electrode or to the grounding electrode system. Table 250.66 sizes it from the largest ungrounded conductor, not from a breaker.

  • EGC: follows the circuit. Input is the overcurrent device rating. Table 250.122.
  • GEC: follows the electrode connection. Input is the largest ungrounded service conductor (or the combined area of parallel sets). Table 250.66.

Table 250.122: sized from the breaker

Find the rating of the overcurrent device ahead of the circuit, then read across. The rating in the table is a ceiling: use the first row whose rating equals or exceeds your device. There is no row between 20 A and 60 A, so a 30, 40 or 50 A breaker uses the 60 A row. Here are some copper and aluminum rows, as listed in several study references:

Overcurrent device (A)Copper EGCAluminum EGC
1514 AWG12 AWG
2012 AWG10 AWG
6010 AWG8 AWG
1008 AWG6 AWG
2006 AWG4 AWG
4003 AWG1 AWG
8001/0 AWG3/0 AWG
12003/0 AWG250 kcmil

Always read the values from the table in your own code book. The rows above are for practice, not for installing anything.

Table 250.66: sized from the service conductors

Here the input is the size of the largest ungrounded service conductor. If the service uses parallel sets, add the circular mil area of all the conductors in one phase and use that total. Copper rows:

Largest ungrounded conductor (copper)Copper GEC
2 AWG or smaller8 AWG
1 or 1/0 AWG6 AWG
2/0 or 3/0 AWG4 AWG
Over 3/0 through 350 kcmil2 AWG
Over 350 through 600 kcmil1/0 AWG
Over 600 through 1100 kcmil2/0 AWG
Over 1100 kcmil3/0 AWG

Side by side

Table 250.122 (EGC)Table 250.66 (GEC)
InputOvercurrent device rating, in amperesLargest ungrounded conductor size
Goes withEach circuit or feederService, or a separately derived system
CarriesGround-fault currentConnection to the electrode
Parallel conductorsSize from the device, not dividedAdd the parallel conductors in one phase

Worked example: one 200 A panel, two answers

A 200 A main breaker feeds a service with 3/0 copper ungrounded conductors. Two sizes are asked for, copper in both cases.

  1. Equipment grounding conductor. The input is the device rating, 200 A. Table 250.122 at 200 A gives 6 AWG copper.
  2. Grounding electrode conductor. The input is the largest ungrounded conductor, 3/0 copper. Table 250.66 at 2/0 or 3/0 gives 4 AWG copper.

Same panel, two different answers, because the two tables ask different questions. Notice also that the GEC came out larger than the EGC. That is normal, and it is a good reason not to assume one number can stand in for the other.

Upsized conductors: the 250.122 increase

If the ungrounded conductors are made larger than the minimum for a reason such as voltage drop, a wire-type EGC must be increased in proportion to the circular mil area of the ungrounded conductors. In the NEC 2020 text this is 250.122(B). The increase does not apply to conductors upsized only for ampacity adjustment or correction.

Example: a 20 A circuit would normally use 12 AWG conductors and a 12 AWG EGC. It is upsized to 10 AWG for voltage drop. 12 AWG is 6,530 circular mils and 10 AWG is 10,380, a ratio of about 1.59. The EGC must now be at least 10,380 circular mils, which is 10 AWG. Circular mil values come from NEC Chapter 9, Table 8.

A related point: the EGC is generally not required to be larger than the circuit conductors it accompanies (250.122(A)). For parallel conductors run in multiple raceways, a full-size EGC sized from the device goes in each raceway (250.122(F)).

The GEC caps in 250.66(A), (B) and (C)

When the GEC is the only connection to certain electrodes, the table result is capped:

  • Rod, pipe or plate electrode: not required to be larger than 6 AWG copper (4 AWG aluminum).
  • Concrete-encased electrode: not required to be larger than 4 AWG copper.
  • Ground ring: not required to be larger than the conductor used for the ring.

So a very large service might read 3/0 in Table 250.66 and still allow 6 AWG copper to a driven rod, if that conductor is the only connection to the rod. If one continuous conductor serves several electrodes, only the portion that is the sole connection to the rod gets the cap.

Common mistakes

  • Using the conductor size to look up Table 250.122, or the breaker rating to look up Table 250.66.
  • Using the 50 A row for a 50 A breaker. There is none, so go up to the 60 A row.
  • Forgetting to increase the EGC when the phase conductors were upsized for voltage drop.
  • Splitting one EGC between parallel raceways instead of running a full-size one in each.
  • Forgetting the 250.66 caps, or applying them when the GEC also serves another electrode.

Where to read the real text

These resources are worth reading alongside your code book. NFPA publishes the code and a NFPA 70 (NEC) page. NFPA also has a grounding and bonding fact sheet that explains both tables. For a walkthrough of 250.122 in the 2020 edition, see this 250.122 training handout. Table values and paragraph letters can change between editions, so confirm them in the edition your jurisdiction has adopted.

Practice it

Choose the input first, then the table. If you want more worked problems in this style, the CircuitDrill course covers them, and the blog has related calculation guides. CircuitDrill is an independent study resource, not affiliated with NFPA or any licensing board. Always follow the adopted code and your AHJ for real work.

Frequently asked questions

What is the difference between Table 250.122 and Table 250.66?

Table 250.122 sizes the equipment grounding conductor from the rating of the overcurrent device protecting the circuit. Table 250.66 sizes the grounding electrode conductor from the largest ungrounded service conductor, or the combined area of parallel sets.

Which row do I use if my breaker is not listed in Table 250.122?

Use the first row whose rating equals or exceeds the overcurrent device. A 50 A breaker, for example, uses the 60 A row. Confirm the rows in the edition your jurisdiction has adopted.

Does the equipment grounding conductor get larger when I upsize for voltage drop?

Yes. When the ungrounded conductors are increased in size for reasons other than ampacity adjustment or correction, a wire-type EGC is increased in proportion to the circular mil area. In the NEC 2020 text this is 250.122(B). Paragraph lettering can differ between editions.

Is the grounding electrode conductor always the size shown in Table 250.66?

Not always. When the GEC is the only connection to a rod, pipe or plate electrode, it is not required to be larger than 6 AWG copper. For a concrete-encased electrode the limit is 4 AWG copper. Check 250.66(A) to (C) in your edition and ask your AHJ.