Overcurrent
Standard Breaker Sizes and the Next Size Up Rule: Common Mistakes
"Which breaker do I put on this conductor?" sounds simple, yet it is a steady source of lost points. The answer depends on two things that are easy to blur together: the list of standard ratings in 240.6(A), and the next size up rule in 240.4(B). This guide walks through both and then goes through the mistakes that show up most often in practice questions.
Edition check: section numbers here follow the NEC 2020 and 2023 editions. Rules about overcurrent devices are revised from cycle to cycle, so confirm the exact wording in the edition your state has adopted, and ask the authority having jurisdiction (AHJ) when in doubt. This is a study aid, not an installation instruction.
The standard ratings: Table 240.6(A)
Standard ampere ratings for fuses and inverse time circuit breakers run in a fixed list. In the range most exam questions use, the list reads:
15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000 and 6000 A.
Notice the gaps. There is no 65, no 75, no 120, and no 900. If a calculation lands on a number that is not in the list, the answer is not "that size". Section 240.6 does allow fuses or inverse time circuit breakers with nonstandard ratings in some cases, but these may not be readily available, and an exam question about standard sizes means the list above.
The next size up rule: 240.4(B)
Overcurrent protection normally protects a conductor at its ampacity. But conductor ampacities seldom match a standard rating. A conductor with an ampacity of 310 A, for example, falls between the 300 A and 350 A ratings. Section 240.4(B) lets you use the next higher standard rating when all of these are true:
- The conductors are not part of a multioutlet branch circuit supplying receptacles for cord-and-plug connected portable loads.
- The ampacity of the conductors does not correspond with a standard rating.
- The next higher standard rating does not exceed 800 A.
The word to underline is permitted. The rule allows the next size up. It does not require it, and it does not force you to ignore a smaller device that suits the circuit.
Worked example: the rule applied correctly
A single 500 kcmil aluminum conductor has an ampacity of 310 A, taken from the ampacity table in Article 310 for the termination temperature in use. That is not a standard rating. The standard ratings on either side are 300 A and 350 A. The circuit is not a multioutlet cord-and-plug receptacle circuit, and 350 A is below the 800 A limit. So a 350 A device is permitted under 240.4(B), provided the load itself does not exceed the 310 A the conductor can carry.
Common mistakes
1. Rounding to a number that is not on the list
A calculated 900 A load does not mean a 900 A breaker. There is no 900 A standard rating. The next step is a different question: what the rule allows when the number lies above 800 A.
2. Using the rule above 800 A
Take three 500 kcmil aluminum conductors in parallel. Together their ampacity is 930 A. The next standard rating above 930 A is 1000 A, but the next size up rule stops at 800 A. A 1000 A device cannot be justified by 240.4(B) here. The other side of the problem is just as real: an 800 A device may be too small for the load. So you must go back to the conductors, the load or the allowed alternatives, rather than rounding up.
3. Forgetting the cord-and-plug exclusion
The first condition removes multioutlet branch circuits that supply receptacles for cord-and-plug connected portable loads. On those circuits, the next size up rule is not available.
4. Ignoring the small conductor limits in 240.4(D)
For the smallest copper sizes, the overcurrent device is capped regardless of what the ampacity table shows:
| Copper conductor | Maximum overcurrent device |
|---|---|
| 14 AWG | 15 A |
| 12 AWG | 20 A |
| 10 AWG | 30 A |
These limits override the next size up rule. So a 12 AWG copper circuit is limited to a 20 A device even when the ampacity table would let you consider a higher number. Section 240.4(D) also contains exceptions for specific cases, so read the full text in your edition.
5. Treating the next size up as a requirement
If the ampacity matches a standard rating, use that rating. If it does not, 240.4(B) permits the next higher one. It does not say you must go up, and it does not replace the other rules that might apply to the equipment or load.
6. Mixing up the conductor with the load
The next size up rule starts from the conductor ampacity. It does not tell you how to calculate a load, and other articles can modify the general overcurrent rules for specific equipment. When a question names a special case, read the article for it.
Quick check
A conductor's ampacity is 65 A and the circuit is not a cord-and-plug receptacle circuit. The standard ratings around 65 A are 60 A and 70 A. Because 65 A is not a standard rating and 70 A is below 800 A, a 70 A device is permitted, as long as no small conductor limit in 240.4(D) applies. A 14, 12 or 10 AWG copper conductor would be capped well below that, so check the conductor size first.
Where to read more
NFPA publishes the code on its NFPA 70 (NEC) page. For the text and a walkthrough of 240.4(B), see the 240.4(B) section reference and this feeder overcurrent protection article with parallel conductor examples. The first covers the 2023 edition; the second was written for an earlier edition, so confirm each point in your own code book.
Practice it
When you meet a breaker question, run the same three checks every time: is the number on the list, is the circuit 800 A or less, and does a small conductor limit apply? The CircuitDrill course has more worked problems in this style, and the blog has related calculation guides. CircuitDrill is an independent study resource, not affiliated with NFPA or any licensing board. Follow the adopted code and your AHJ for real work.
Frequently asked questions
What are the conditions for the next size up rule in 240.4(B)?
The conductors must not be part of a multioutlet branch circuit supplying receptacles for cord-and-plug connected portable loads, the conductor ampacity must not correspond with a standard rating, and the next higher standard rating must not exceed 800 A. Confirm the wording in your adopted edition.
Is 900 A a standard overcurrent device rating?
No. The standard ratings in 240.6(A) go from 800 to 1000 to 1200 A. There is no 900 A rating on the standard list.
Does the next size up rule apply to 14, 12 and 10 AWG copper?
The small conductor limits in 240.4(D) override it. For copper, 14 AWG is limited to 15 A, 12 AWG to 20 A and 10 AWG to 30 A, subject to the exceptions in that section.
Is the next size up rule required?
No. It permits the next higher standard rating when the ampacity does not match a standard size. It does not require you to go up, and other rules may still apply to the load or equipment.
Free
Get 5 worked problems right away
Voltage drop, conduit fill, box fill, Ohm's law and derating. One problem each, solved line by line. They open right after you sign up.
Voltage drop calculator with every step shown
Single-phase or three-phase, copper or aluminum, 14 AWG to 500 kcmil.