Why do water heaters, dryers and other big loads run on 240 V instead of 120 V? The short answer is that for the same power, a higher voltage means less current, and less current means much less energy lost in the wire. Exams ask this in several forms: what happens to the current, the voltage drop or the loss when the voltage doubles. This guide shows the math with one worked example, so you can answer all of them with the same two formulas.

The two formulas

OpenStax gives the electric power relationships in University Physics Volume 2, Electrical Energy and Power: P = IV for any device, and P = I²R for the power dissipated in a resistance. From them:

  • Current for a given load: I = P / V. Same watts, double the voltage, half the current.
  • Loss in the wire: P(loss) = I² × R, where R is the resistance of the conductors. Half the current means one quarter of the loss, because the current is squared.

Two more results follow. The voltage drop in volts is I × R, so it halves with the current. As a share of the source voltage it is I × R / V, so it drops to one quarter, because the current halves and the voltage doubles.

What the textbook example shows

Kuphaldt's open textbook, Lessons in Electric Circuits, Volume II, compares the same total power at two voltages. Two 10 kW loads on 120 V draw 83.33 A each, 166.66 A in total, and the text says the wire would have to be substantial, at least 1/0 copper. Put the same loads on 240 V and the total current is 83.33 A, half as much, and the text says number 4 wire can now be used. The load did not change. Only the voltage did.

Worked example: 4,800 W at three voltages

Take a 4,800 W resistive load at the end of 100 ft of 8 AWG copper, so there is 200 ft of conductor out and back. First find the resistance of the wire at 20°C. A Navy-based conductor table lists copper at 10.37 ohm-circular-mils per foot (CED Engineering), and a copper wire table lists 8 AWG as about 16,500 circular mils (Ness Engineering).

  • R = 10.37 × 200 / 16,500 = 0.126 ohm

Now compare the three voltages, using I = P / V, VD = I × R and loss = I² × R.

SupplyCurrentVoltage dropPercent dropWire loss
120 V40 A5.03 V4.19%201 W
240 V20 A2.51 V1.05%50.3 W
480 V10 A1.26 V0.26%12.6 W

Every doubling of the voltage halves the current and the voltage drop, and cuts the percent drop and the wire loss to a quarter. Check one entry by hand: at 120 V, loss = 40² × 0.1257 = 201 W. Using the rounded 0.126 ohm gives 201.6 W, which is why the last digit can differ.

Notice that the percent drop and the loss as a share of the load power are the same number. 201 W out of 4,800 W is 4.2 percent, and the drop is 5.03 V out of 120 V, also 4.2 percent. That is not a coincidence: I²R / (V × I) = I × R / V.

Read the example for what it is

This is a thought experiment about the physics. Real equipment is built for a specific voltage, so you cannot freely move a load to another voltage. The 40 A case in particular is only a comparison. Conductor sizes, ampacities and overcurrent protection come from the National Electrical Code edition adopted in your state and from your authority having jurisdiction (AHJ), and none of that is covered here.

Three exam variations

  • "The voltage is doubled and the load stays the same. What happens to the current?" It is cut in half.
  • "What happens to the I²R loss in the same conductors?" It falls to one quarter.
  • "Which supply gives the smaller percent voltage drop for the same load?" The higher voltage. At double the voltage the percent drop is one quarter.

Common mistakes

  • Saying the loss halves. Loss depends on current squared, so it quarters.
  • Thinking a higher voltage means more current. For the same watts it means less.
  • Mixing up volts and percent. The drop in volts halves. The drop as a percent quarters.
  • Using the one-way length. The conductors run out and back, so use twice the one-way distance for the resistance.
  • Changing the load. The comparison holds the watts constant. A different load is a different problem.

Self-check

A 3,000 W resistive load runs at 120 V and then at 240 V. What are the currents?

3,000 / 120 = 25 A, and 3,000 / 240 = 12.5 A.

The current in a conductor drops from 30 A to 15 A. What happens to the I²R loss?

It drops to one quarter: 15² is 225 and 30² is 900.

Same load, same wire, supply voltage goes from 240 V to 480 V. What happens to the percent voltage drop?

It falls to one quarter.

Keep practicing

To see the voltage drop side of this with the standard formulas, read the voltage drop guide and try the free voltage drop calculator. For timed practice, the CircuitDrill Calculations Course has 308 exercises and four timed practice exams for a one-time $59. See the course page. CircuitDrill is an independent study tool, not affiliated with NFPA, the National Electrical Code, or any state licensing board.

Frequently asked questions

What happens to current when voltage doubles for the same load?

The current is cut in half, because I = P / V.

Why does wire loss fall to one quarter, not one half?

Loss in a conductor is I squared times R. Half the current means (1/2) squared, which is one quarter.

Is the percent voltage drop also lower at a higher voltage?

Yes. The drop in volts halves and the supply voltage doubles, so the percent drop falls to one quarter.

Can I move any load to a higher voltage to reduce loss?

No. Equipment is built for a specific voltage. The comparison is a physics exercise, and real installations follow the adopted code edition and the AHJ.

FREE TOOL

Voltage drop calculator with every step shown

Single-phase or three-phase, copper or aluminum, 14 AWG to 500 kcmil.