Open Neutral on 120/240 V: Why One Load Gets More Than 120 V

/ 7 min read / By CircuitDrill

Here is a concept that shows up on exams in several disguises: a 120/240 V circuit loses its neutral connection. What voltage does each load see? The tempting answer is still 120 V. The correct answer depends on the loads, and one of them can end up with far more voltage than it was built for. This guide explains why with plain series-circuit math, works an example, and points to a real incident report.

What the neutral does

In a 120/240 V system, each 120 V load is connected between one hot conductor and the neutral. Kuphaldt's open textbook, Lessons in Electric Circuits, Volume II, explains the logic. Two 120 V loads could be connected in series across the 240 V between the hot conductors, but then if one load opened, current would stop in the other as well. The neutral wire is added so that each load can be driven individually.

With balanced loads the neutral carries zero current, as the same textbook notes. With unbalanced loads it carries the difference. That is why a missing neutral does nothing when the loads are exactly equal, and does a lot when they are not.

What happens when the neutral opens

Take the neutral away and the two loads end up in series across the 240 V. In a series circuit, the same current flows through both, and, as OpenStax puts it in Resistors in Series and Parallel, the individual resistors do not get the total source voltage but divide it. Each load gets a share equal to its resistance divided by the total:

  • V1 = 240 × R1 / (R1 + R2)
  • V2 = 240 × R2 / (R1 + R2)

The load with the larger resistance, which is the one that draws less power at 120 V, gets the larger share of the voltage.

Myth versus fact

MythFact
With the neutral open, each 120 V load still gets 120 V.The loads share 240 V in proportion to their resistance. Only equal loads get 120 V each.
The bigger load, the one drawing more power, gets the most voltage.The smaller load, the one with more resistance, gets the higher voltage.

Problem 1: 1,200 W and 300 W loads

A 1,200 W load is on one side and a 300 W load is on the other. Both are rated 120 V. The neutral opens. Find the voltage on each load.

  • Resistance from P = V² / R (see OpenStax, Electrical Energy and Power): R = V² / P
  • R1 = 120² / 1,200 = 12 ohm
  • R2 = 120² / 300 = 48 ohm
  • Series total = 12 + 48 = 60 ohm
  • I = 240 / 60 = 4 A
  • V1 = 4 × 12 = 48 V
  • V2 = 4 × 48 = 192 V
  • Check: 48 + 192 = 240 V

The 300 W load is now at 192 V, which is 60 percent above its 120 V rating. If the load stayed at a fixed resistance, it would dissipate 4² × 48 = 768 W instead of 300 W, which is 2.56 times its rating. The 1,200 W load, meanwhile, would get only 48 V and would dissipate 192 W.

How it scales

Keep the 1,200 W load and change the load on the other side:

Other loadVoltage on 1,200 W loadVoltage on other load
1,200 W120 V120 V
600 W80 V160 V
300 W48 V192 V
100 W18.5 V221.5 V

The more unequal the loads, the closer the small load gets to the full 240 V.

Problem 2: equal loads

Two 600 W loads, one on each side. R = 120² / 600 = 24 ohm each. Series total = 48 ohm, I = 240 / 48 = 5 A, and each load gets 5 × 24 = 120 V. Nothing changes, because with perfectly balanced loads the neutral carried no current to begin with.

A real-world example

Technical Safety BC published an incident summary for a February 2021 event at Cowichan Bay. The cause was a loose termination in a meter base: the neutral lug had not been tightened. The report says that with an open neutral, the voltage on each 120 V side may vary between 0 and 240 V depending on the load difference between the two lines. It lists flickering, dimming and brightening of lights and overvoltage damage to 120 V appliance components as possible effects, and records voltages reaching at least 204 V at a surge protective device in this case. You can read the full document at Technical Safety BC, Incident Summary #II-1140811-2021.

The limits of the simple model

The calculation above treats each load as a fixed resistance. Real loads change as voltage and temperature change, and motors and electronics do not behave like resistors, so real voltages will differ. The point for the exam is the method: a missing neutral turns two loads into a voltage divider, and the smaller load gets the higher voltage.

This guide is theory only. An open neutral is a hazard. If lights flicker, dim or brighten as other loads switch on and off, call a licensed electrician or your utility, and do not open panels or meter bases yourself.

Common mistakes

  • Assuming each load still gets 120 V. Only equal loads do.
  • Thinking the bigger load gets more voltage. The smaller load, with the higher resistance, does.
  • Using 120 V as the total. The loads are in series across 240 V.
  • Using watts instead of resistance. Convert each load with R = V² / P first, then divide the voltage.

Self-check

Two equal loads share a circuit and the neutral opens. What does each see?

120 V each. Equal resistances split 240 V evenly.

A 600 W load and a 150 W load, both rated 120 V, lose their neutral. Which gets the higher voltage?

The 150 W load. R1 = 24 ohm and R2 = 96 ohm, so I = 240 / 120 = 2 A. The 150 W load gets 192 V and the 600 W load gets 48 V.

Why does a perfectly balanced circuit not care about losing its neutral?

Because the neutral was carrying no current. Equal loads already split the voltage evenly.

Keep practicing

This guide explains the circuit theory behind open neutral questions. Wiring rules and safe practices come from the National Electrical Code edition adopted in your state and your authority having jurisdiction (AHJ), so check both. For timed practice on Ohm's law, series circuits and load problems, see the Ohm's law guide and the CircuitDrill Calculations Course, which has 308 exercises and four timed practice exams for a one-time $59. See the course page. CircuitDrill is an independent study tool, not affiliated with NFPA, the National Electrical Code, or any state licensing board.

Frequently asked questions

What voltage does each load see if the neutral opens on a 120/240 V circuit?

The two loads end up in series across 240 V and share it in proportion to their resistance. Only equal loads get 120 V each.

Which load gets the higher voltage with an open neutral?

The load with the larger resistance, which is the smaller load in watts.

Why does losing the neutral not matter when the loads are balanced?

With perfectly balanced loads the neutral carries no current, so equal loads already split the voltage evenly.

What problems can an open neutral cause?

Technical Safety BC lists flickering, dimming and brightening of lights and overvoltage damage to 120 V appliance components. Call a licensed electrician or your utility if you notice symptoms.