Resistance
Wire Resistance: Length, Size, Copper vs Aluminum and Temperature
Every wire is a resistor, and its resistance decides how much voltage and power you lose along the run. Exam problems come at this from several angles: a longer run, a smaller conductor, aluminum instead of copper, a hotter conductor. This guide puts a number on each of the four levers, using published physics and wire data, and ends with a check against the K value used in voltage drop problems.
The formula
The resistance of a uniform conductor is R = ρ × L / A, where ρ (rho) is the resistivity of the material, L is the length and A is the cross-sectional area. OpenStax gives this as Equation 9.9 in University Physics Volume 2, Resistivity and Resistance: the longer the conductor, the greater its resistance, and the larger its area, the smaller its resistance.
Electricians usually work in feet and circular mils, so the same formula is used with resistivity in ohm-circular-mils per foot. The CED Engineering conductor course, adapted from a U.S. Navy training manual, lists these values at 20°C.
| Material | ρ at 20°C (OpenStax) | ρ at 20°C (Navy-based table) |
|---|---|---|
| Copper | 1.68 × 10⁻⁸ ohm-meter | 10.37 ohm-CM per ft |
| Aluminum | 2.65 × 10⁻⁸ ohm-meter | 17.02 ohm-CM per ft |
The two sources are not identical. Aluminum divided by copper is 1.58 in the OpenStax table and 1.64 in the Navy-based one. Both say the same thing: for equal length and area, aluminum has roughly 1.6 times the resistance of copper. On the exam, use the value the problem gives you.
Problem 1: copper, 12 AWG
A branch circuit runs 100 ft one way on 12 AWG copper. Find the resistance of the conductors, out and back, at 20°C. The area of 12 AWG is 6,530 circular mils.
- Conductor length = 2 × 100 = 200 ft
- R = 10.37 × 200 / 6,530 = 0.318 ohm
- Check: a copper wire table lists 1.59 ohms per 1,000 ft for 12 AWG (Ness Engineering), and 1.59 × 0.2 = 0.318 ohm
Problem 2: the same circuit in aluminum
- R = 17.02 × 200 / 6,530 = 0.521 ohm
- Ratio to copper = 0.521 / 0.318 = 1.64
Same size, same length, and aluminum loses about 64 percent more voltage at the same current.
Problem 3: temperature
Resistance rises with temperature. OpenStax gives R = R₀(1 + αΔT), with R₀ taken at 20°C, and lists α = 0.0039 per °C for both copper and aluminum. Take the copper circuit from Problem 1 and heat the conductors to 75°C.
- ΔT = 75 minus 20 = 55°C
- Factor = 1 + 0.0039 × 55 = 1.2145
- R = 0.318 × 1.2145 = 0.386 ohm, about 21 percent higher
The Navy-based source gives a copper coefficient of 0.00427, measured from 0°C. Working from that figure gives the same 0.386 ohm. For aluminum at 75°C the same factor gives 0.521 × 1.2145 = 0.633 ohm.
Problem 4: how much bigger must aluminum be?
To get the same resistance as the 12 AWG copper, aluminum needs more area. Using the Navy-based ratio:
- Area needed = 1.64 × 6,530 = 10,720 CM
- 10 AWG is about 10,380 CM, which is about 3 percent short, so matching copper's resistance takes a bit more than two AWG sizes
The rule that every 3 AWG sizes doubles the area (from the AWG reference) puts a ratio of 1.64 at about 2.1 sizes. The OpenStax ratio of 1.58 would land at about 2.0. Either way, the answer is about two sizes. This is a resistance comparison only. Conductor sizing for real installations also depends on ampacity and the code tables, which this guide does not cover.
Where K comes from
The voltage drop guide uses K = 12.9 for copper and 21.2 for aluminum at 75°C. Those are resistivity values at a working temperature. Start with 10.37 at 20°C and apply the temperature factor: 10.37 × 1.2145 = 12.6. For aluminum, 17.02 × 1.2145 = 20.7. Both land within about 2.5 percent of the K values, and the ratio of the two K values, 21.2 / 12.9 = 1.64, matches the aluminum to copper ratio above. So K is not a mystery number. It is resistivity, at a hot conductor temperature.
Common mistakes
- Using the one-way length for the resistance of the loop. A circuit has an outgoing and a return conductor, so the conductor length is twice the one-way distance.
- Forgetting the temperature. A table value is stated for a specific temperature. Use the one the problem names.
- Reversing the area effect. A bigger area means less resistance.
- Mixing resistivity units. Ohm-meter values go with square meters. Ohm-CM per foot values go with feet and circular mils.
- Treating equal resistance as equal ampacity. They are different questions.
Self-check
A copper run measures 0.30 ohm. You double the length and double the area. What is the new resistance?
0.30 ohm. Doubling the length doubles the resistance, and doubling the area cuts it in half.
Does a hotter copper conductor have more or less resistance?
More. For copper, resistance rises about 0.39 percent per degree Celsius.
Which has more resistance for the same size and length, copper or aluminum?
Aluminum, by roughly a factor of 1.6.
Keep practicing
This guide explains the physics behind resistance and voltage drop questions. It is not a sizing guide. Conductor sizes, temperature ratings and ampacities for real installations come from the National Electrical Code edition adopted in your state and your authority having jurisdiction (AHJ). To practice voltage drop and Ohm's law problems under time pressure, try the free voltage drop calculator and the CircuitDrill Calculations Course, which has 308 exercises and four timed practice exams for a one-time $59. See the course page. CircuitDrill is an independent study tool, not affiliated with NFPA, the National Electrical Code, or any state licensing board.
Frequently asked questions
How do you calculate the resistance of a wire?
R = resistivity x length / area. With feet and circular mils, copper is 10.37 ohm-CM per foot and aluminum is 17.02 at 20 degrees C. For a circuit, use the full out-and-back conductor length.
How much more resistance does aluminum have than copper?
About 1.6 times for the same size and length. OpenStax values give 1.58 and a Navy-based table gives 1.64.
How does temperature change wire resistance?
Resistance rises with temperature. OpenStax lists a coefficient of 0.0039 per degree C for copper and aluminum, so a 55 degree rise adds about 21 percent.
Where does K = 12.9 in the voltage drop formula come from?
K is the resistivity of copper in ohm-CM per foot at a working temperature. 10.37 at 20 degrees C scaled for 75 degrees C gives about 12.6, close to 12.9.