Code rules
Tap Rules Compared: 10 ft vs 25 ft Under NEC 240.21(B)
Normally, a conductor must be protected at its ampacity. Section 240.21 is where the code makes exceptions, and the feeder tap rules in 240.21(B) are the ones that show up most often on exams and in switchgear. The 10 ft tap and the 25 ft tap look alike, so people mix them up. This article puts them side by side.
Section numbers and fractions below follow the 2020 and 2023 editions of NFPA 70, as described in the sources at the end. Subsection wording changes between code cycles, so read the actual text in the edition your state has adopted, and ask the authority having jurisdiction (AHJ) when you are not sure.
What a tap is
A feeder tap is a smaller conductor connected to a feeder, with no overcurrent device at the point where the tap begins. Because the smaller conductor is not protected there, the code limits how long it can be, how big it must be compared with the feeder protection, and where it must end. The two limits you need to know first are length and the fraction of the feeder overcurrent device rating.
10 ft tap versus 25 ft tap
| 10 ft tap, 240.21(B)(1) | 25 ft tap, 240.21(B)(2) | |
|---|---|---|
| Maximum length | 10 ft | 25 ft |
| Fraction of the feeder device rating | At least one tenth, where the tap leaves the enclosure | At least one third |
| Also at least | The calculated load, and the rating of the device the tap supplies | The calculated load, and the rating of the device the tap supplies |
| Where it ends | At the equipment it supplies | In a single circuit breaker or one set of fuses that limits the load to the tap ampacity |
| Physical protection | Protected from physical damage | Protected from physical damage, in practice a raceway or other approved means |
The key point: the fraction is based on the rating of the overcurrent device protecting the feeder, not on the size of the feeder conductor. If a 600 kcmil feeder is protected by a 400 A breaker, you use 400 A.
Example 1: a 25 ft tap from a 400 A feeder device
- The feeder is protected by a 400 A overcurrent device.
- One third of 400 A is 133.3 A. That is the minimum tap ampacity.
- 1 AWG copper is 130 A in the 75°C column of Table 310.16. That falls just short.
- 1/0 AWG copper is 150 A in the 75°C column. That works.
The tap must also end in a single breaker or one set of fuses that limits the load to the ampacity of the tap, and it must be protected from physical damage. Temperature limits at the terminals still apply, as covered in our guide to 60°C and 75°C terminal ratings.
Example 2: a 10 ft tap on the same 400 A feeder
- One tenth of 400 A is 40 A.
- That is only a floor. The tap must also carry the calculated load and at least match the device it supplies.
- If the tap feeds a 60 A device, the minimum is 60 A, not 40 A.
This is the part people miss. The fraction is one condition of several. The tap has to satisfy all of them, and the largest requirement wins.
Example 3: a smaller feeder
A feeder is protected by a 200 A device and you want a 25 ft tap. One third of 200 A is 66.7 A. 6 AWG copper is 65 A in the 75°C column, so it falls short. 4 AWG copper is 85 A, so it is enough on the fraction alone. For a 10 ft tap on the same feeder, the fraction is 20 A, and the load and the device it supplies will almost always be the larger number.
Compare the minimums
| Feeder device | 10 ft tap, one tenth | 25 ft tap, one third |
|---|---|---|
| 200 A | 20 A | 66.7 A |
| 300 A | 30 A | 100 A |
| 400 A | 40 A | 133.3 A |
| 600 A | 60 A | 200 A |
These are only the fraction minimums. Always check the load, the device the tap supplies, and the conductor temperature limits as well.
Other tap rules exist
Section 240.21 also covers taps from transformer secondaries in 240.21(C), including a 25 ft secondary tap, which uses the voltage ratio of the transformer in the one third calculation. Those rules have their own conditions. This article is about the two feeder taps in 240.21(B). For the transformer side of the exam, see our guide to transformer sizing.
Common mistakes
- Taking the fraction of the feeder conductor ampacity instead of the rating of the overcurrent device protecting the feeder.
- Using one tenth when the tap is 25 ft long, or one third when it is 10 ft.
- Letting a 25 ft tap fan out to several devices. It must end in a single breaker or one set of fuses.
- Forgetting that a tap must be protected from physical damage.
- Stopping at the fraction and ignoring the calculated load and the rating of the device the tap supplies.
Where to read more
The NEC is published by NFPA and can be read free online with an account at NFPA 70 on nfpa.org. Electrical Contractor magazine has a worked column on 10 ft and 25 ft feeder tap examples, though it is older and may not match the current edition. A newer explanation with worked sizing is available in a guide to the 10 ft, 25 ft and transformer secondary taps, and another practical summary is in the Anvilfield field guide to feeder taps. Use the code book for the exact conditions.
Practice
For more worked calculations, the CircuitDrill calculations course covers the math side of the journeyman exam, and the blog index lists the rest of the guides. CircuitDrill is an independent study tool and is not affiliated with NFPA, the NEC or any exam provider.
Frequently asked questions
What is the difference between the 10 ft tap and the 25 ft tap?
The 10 ft tap uses a minimum of one tenth of the feeder overcurrent device rating where it leaves the enclosure, and the 25 ft tap uses one third and must end in a single breaker or one set of fuses. Both must also carry the calculated load and be protected from physical damage.
Is the tap fraction based on the feeder wire or the feeder breaker?
It is based on the rating of the overcurrent device protecting the feeder, not the ampacity of the feeder conductor.
What is the minimum 25 ft tap ampacity for a 400 A feeder device?
One third of 400 A is 133.3 A. In the 75°C column, 1 AWG copper at 130 A falls short and 1/0 AWG copper at 150 A works, subject to the other conditions.
Is the one tenth fraction the only limit on a 10 ft tap?
No. The tap must also be at least the calculated load and at least the rating of the device it supplies, so a 60 A device on a 400 A feeder needs a 60 A minimum even though one tenth is 40 A.
Free
Get 5 worked problems right away
Voltage drop, conduit fill, box fill, Ohm's law and derating. One problem each, solved line by line. They open right after you sign up.
Voltage drop calculator with every step shown
Single-phase or three-phase, copper or aluminum, 14 AWG to 500 kcmil.