Wye vs Delta: Line and Phase Voltage and Current Explained

/ 6 min read / By CircuitDrill

Three-phase questions on the journeyman exam often turn on one thing: knowing whether the number in front of you is a line value or a phase value. Get that right and the rest is a multiplication by 1.732. Get it wrong and every answer after it is off. This guide defines the four terms, gives the rules for wye and delta connections, and works three problems you can check line by line.

Four terms to keep straight

  • Line voltage: the voltage measured between any two line conductors.
  • Phase voltage: the voltage across one component, meaning one source winding or one load element.
  • Line current: the current in one line conductor, between the source and the load.
  • Phase current: the current through one component of the source or load.

These definitions follow Tony Kuphaldt's open textbook, Lessons in Electric Circuits, Volume II, Three-phase Y and Delta Configurations. In a balanced system all three lines carry the same current and all three phases are equal, so one calculation covers all three.

The rules for wye and delta

A wye (Y) connection joins one end of each of the three components at a common point. A delta connection joins the three components end to end in a triangle. For a balanced circuit the relationships are:

QuantityWye (Y)Delta
Line voltage1.732 × phase voltageEqual to phase voltage
Line currentEqual to phase current1.732 × phase current
Neutral pointAvailableNot available

The textbook states it in words: in a Y circuit the line currents equal the phase currents and the line voltage is greater than the phase voltage by the square root of 3. In a delta circuit the line voltage equals the phase voltage and the line current is the phase current times the square root of 3. The number 1.732 is the square root of 3, rounded. The MIT power systems text by Kirtley gives the same factor for line-to-line voltage in a wye, and notes that a delta connection has no neutral point, as discussed in Introduction to Electric Power Systems, Line-Line Voltages.

A memory aid: wye splits the voltage, delta splits the current. In a wye, each element sees only part of the line voltage. In a delta, each element sees the full line voltage, and the line current is larger than the current in any one element.

Where 208 V and 480 V come from

A wye source with 120 V across each winding gives 120 × 1.732 = 207.8 V between lines, which is called 208 V. A wye source with 277 V per winding gives 277 × 1.732 = 479.8 V, which is called 480 V. The Michigan Tech lecture notes for EET2233 list 120/208 V and 277/480 V as standard wye systems, and 240 V and 480 V as delta systems. Kuphaldt's chapter on three-phase power systems notes that 208 V is a rounded figure.

This is why a 120/208 V system is not a 120/240 V system, and why your answer changes if you use 240 where 208 belongs.

Problem 1: three heating elements in delta

A heater bank has three 10 ohm elements connected in delta on a 208 V three-phase supply. Find the phase current, the line current, and the total power.

  • In delta, phase voltage equals line voltage: 208 V
  • Phase current = 208 / 10 = 20.8 A
  • Line current = 1.732 × 20.8 = 36.03 A
  • Total power = 3 × 208 × 20.8 = 12,979 W, about 13.0 kW
  • Check: 1.732 × 208 × 36.03 = 12,980 W, the same within rounding

Problem 2: the same elements in wye

Now take the same three 10 ohm elements and connect them in wye on the same 208 V supply.

  • Phase voltage = 208 / 1.732 = 120.1 V
  • Phase current = 120.1 / 10 = 12.01 A, and in a wye the line current is the same 12.01 A
  • Total power = 3 × 120.1 × 12.01 = 4,327 W

The delta bank drew 12,979 W. The wye bank draws 4,327 W. The ratio is 3.0.

Why delta draws three times the power

In delta each element sees the full 208 V. In wye each element sees 120.1 V. Power in a resistance changes with the square of the voltage, and (208 / 120.1)² = 3.0. Kirtley's text gives the same relationship for balanced loads: a delta-connected impedance is three times the wye-connected impedance that draws the same line current (Z delta = 3 × Z wye). So three 10 ohm elements in delta pull the same line current as three 3.33 ohm elements in wye.

Exam writers like this one. They give you a set of elements, reconnect them, and ask what changes. Resist the urge to reconnect real heating equipment from one configuration to the other. Equipment is built for a specific connection and supply, so follow its nameplate and the manufacturer's instructions.

Problem 3: phase current from line current

A balanced delta load draws 30 A on each line. What is the phase current?

  • Delta: line current = 1.732 × phase current
  • Phase current = 30 / 1.732 = 17.3 A
  • Check: 17.3 × 1.732 = 29.97 A, which rounds back to 30 A

Kuphaldt's textbook example shows the same factor going the other way: a delta load with 83.33 A in each phase has 144.34 A in each line, and 83.33 × 1.732 = 144.3. If the same question described a wye load, the trap answer would be to apply 1.732 at all. In a wye the line current simply equals the phase current.

Common mistakes

  • Using 1.732 on the current in a wye. Wye line current equals phase current.
  • Using 1.732 on the voltage in a delta. Delta line voltage equals phase voltage.
  • Multiplying when you should divide. Going from phase to line multiplies by 1.732 where the rule applies. Going from line to phase divides.
  • Reading 208 as 240. They come from different systems.
  • Forgetting the connection change. The same elements draw three times the power in delta that they draw in wye.

The same 1.732 shows up in the three-phase power and voltage drop formulas. For those, see the guides on power factor, kW, kVA and amps and voltage drop.

Self-check

A wye source is rated 277/480 V. What is the phase voltage?

277 V. Dividing the 480 V line voltage by 1.732 gives 277 V.

A balanced wye load has 15 A in each phase. What is the line current?

15 A. In a wye the line current equals the phase current.

A balanced delta load has 20.8 A in each phase. What is the line current?

36.03 A. In delta the line current is 1.732 times the phase current.

Keep practicing

This guide covers the circuit theory behind exam questions. It does not replace the National Electrical Code edition adopted in your state or the rules of your authority having jurisdiction (AHJ), so check both. To practice problems like these under time pressure, the CircuitDrill Calculations Course has 308 exercises and four timed practice exams for a one-time $59. See the course page. CircuitDrill is an independent study tool, not affiliated with NFPA, the National Electrical Code, or any state licensing board.

Frequently asked questions

What is the difference between line voltage and phase voltage?

Line voltage is measured between two line conductors. Phase voltage is measured across one source winding or one load element. In a balanced wye the line voltage is 1.732 times the phase voltage. In a delta they are equal.

Where does 208 V come from?

A wye source with 120 V across each winding gives 120 x 1.732 = 207.8 V between lines, which is rounded to 208 V.

In which connection is line current 1.732 times phase current?

In a balanced delta. In a wye, the line current equals the phase current.

Why do the same three elements draw more power in delta than in wye?

In delta each element sees the full line voltage, 1.732 times the wye value. Power in a resistance goes with the square of voltage, so the delta connection draws three times the power.